What Changed About Hazard Mitigation Analysis in the 2026 NFPA 855?

The 2026 edition of NFPA 855 updates hazard mitigation analysis (HMA) requirements for stationary energy storage systems (ESS). The most significant change is the removal of the “maximum allowable quantity” thresholds in Table 9.4.1, which means many more systems may now require a site-specific HMA.

Engineers, installers, EPCs, and manufacturers working with lithium-ion battery energy storage systems should understand where the HMA requirements sit in the standard, what the analysis evaluates, and how it connects to emergency response planning and explosion control.

What NFPA 855 Covers

NFPA 855 is the standard for the installation of stationary energy storage systems, and it also applies to portable ESS used in a stationary manner. Its purpose is to establish minimum requirements that reduce the hazards associated with these systems. The standard specifically calls out lithium-ion batteries, although parts of Chapter 4 apply to other chemistries as well.

Chapter 4 contains the general requirements that apply to all energy storage systems. Chapters 9 through 13 address specific technologies in more detail. Electrochemical systems, including lithium-ion, lead-acid, and nickel-based batteries, fall under Chapter 9.

Want to Go Deeper on NFPA 855?

We offer an online workshop that covers NFPA 855 in greater detail, giving project teams a more thorough understanding of the standard and its requirements. Register for the NFPA 855 online workshop to build a stronger command of the standard before your next energy storage project.

Where Does the HMA Requirement Live in the Standard?

The HMA requirement appears in Section 4.4 of Chapter 4. Because Chapter 4 sets out the standard's general requirements, the HMA requirement applies to all energy storage technologies by default. Under this section, a hazard mitigation analysis must be provided to the AHJ for review and approval.

The one exception is when the technology-specific chapter states otherwise. Chapter 9 contains its own HMA provisions for electrochemical systems, which can modify how Section 4.4 applies. Anyone working on a lithium-ion project should review both sections to confirm which requirements apply to their system.

Chapter 9 Exceptions and AHJ Authority

New language in Chapter 9 provides a pathway for lead-acid and nickel-based batteries to proceed without an HMA. Lithium-ion systems do not receive this exception. As a result, the analysis remains a requirement for the chemistry used in most battery energy storage systems.

Chapter 9 also authorizes the AHJ to require adjustments to a system’s mitigation and protection measures based on the analysis's findings. This allows the AHJ to respond directly to the hazards the HMA identifies. The section also addresses unlisted products, providing the AHJ with additional oversight when a product lacks a listing.

Why Was the 600 kWh Threshold Removed?

The 2023 edition of NFPA 855 used a table of maximum allowable quantities, or maximum stored energy, to determine when an HMA was required (see: Table 9.4.1). Systems above 20 kWh per fire area fell within the scope of the standard. A site-specific HMA, however, only became mandatory above 600 kWh per fire area.

The 2026 edition removes that threshold. The 600 kWh figure was a semi-arbitrary limit, and smaller systems still carry risks that warrant analysis. A 400 kWh per fire area system, for example, falls under 600 kWh but nonetheless presents hazards that should be considered, analyzed, and mitigated. By removing Table 9.4.1 many more systems will now require a site-specific HMA.

What an HMA Evaluates

An HMA is a technical report that is reviewed and stamped by a licensed fire protection engineer. HMAs use data-centric language intended for a technical audience. The fire service and the surrounding community are not the intended readers, as that role belongs to the emergency response plan.

The analysis works by assessing BESS failure modes and their respective approval conditions.. For example, thermal runaway is one failure mode addressed by an HMA and remains a primary concern across the industry. An HMA also includes failure modes related to balance of system components and other components within a BESS, along with space for failure modes that the AHJ in a specific jurisdiction may want addressed.

Gas Detection and Explosion Control for LFP Systems

Failures in gas detection and in explosion control and prevention are among the failure modes considered in an HMA. These are especially relevant for lithium-ion batteries with a lithium-iron-phosphate (LFP) cathode. LFP is the chemistry most commonly used in stationary battery energy storage systems today.

LFP batteries generally offer good thermal runaway stability in that they have a higher thermal runaway onset temperature than comparable lithium-ion chemistries. However, LFP cells also produce flammable off-gases. Evaluating how gas detection and explosion control systems could fail is therefore a critical part of the HMA for these systems.

How Does an HMA Support Emergency Response Planning?

The HMA requirements also ask the analysis to consider the impacts of a failure event with the emergency response plan in mind. This includes determining what an evacuation plan might look like if an incident were to occur at a facility with a lithium-ion battery system. The analysis also informs how responders should approach the event.

The standard further specifies why the analysis should be delivered and to whom. In many cases, the audience is the fire marshal acting as the AHJ. Identifying that audience early helps ensure the analysis supports the decisions the AHJ will need to make during review.

The Connection to NFPA 68 and NFPA 69

Explosion control and prevention systems are also a required consideration within the HMA. This requirement serves as the pathway in NFPA 855 to NFPA 68 and NFPA 69. Manufacturers, installers, and EPCs already working with those standards will find that the HMA connects directly to that work.

Systems developed under NFPA 68 and NFPA 69 can address concerns uncovered through the hazard mitigation analysis. This makes coordination between the HMA and explosion control design an important part of the project process. As more systems are subject to the HMA requirement in the 2026 edition, this connection will apply to a wider range of projects.

Conclusion

The removal of the 600 kWh threshold in the 2026 edition of NFPA 855 means that hazard mitigation analysis will be part of many more energy storage projects going forward. Understanding what the HMA requirements are, what an HMA evaluates, and how it connects to emergency response planning and explosion control will help project teams prepare for AHJ review. This is especially true for lithium-ion and LFP systems, which do not receive the exceptions available to other chemistries.

Mayfield Renewables provides engineering, consulting, and education services for teams navigating code compliance and safety standards for battery energy storage, microgrids, and PV plus BESS projects. Training is available through online courses and custom sessions delivered in person or online on a quarterly retainer basis. Questions about HMAs or a specific project can be sent to education@mayfield.energy.